A Voltage-Ratio Fixed-Point Formulation for Power Flow Analysis in Single-Phase AC Distribution Networks with Certified Convergence

Authors

DOI:

https://doi.org/10.19139/soic-2310-5070-4665

Keywords:

Power flow, Fixed-point iteration, Banach fixed-point theorem, Voltage-ratio formulation, Radial and meshed networks, Convergence analysis, Distribution systems

Abstract

This paper proposes a voltage-ratio fixed-point formulation for the power-flow analysis of balanced AC distribution networks with either radial or meshed topologies. The classical nodal power-flow equations are recast exactly in terms of inverse squared-voltage magnitude variables and pairwise complex voltage-ratio variables, and then compactly normalized with respect to the unique slack-bus voltage. The resulting normalized power-flow equations define a natural fixed-point mapping whose nonlinearity is confined to an element-wise reciprocal of the conjugated normalized voltage vector, thereby avoiding the explicit construction of the inverse of the reduced nodal admittance matrix. A convergence analysis is developed using the Banach fixed-point theorem. Sufficient conditions for the existence and uniqueness of the power-flow solution, as well as for the at-least-linear convergence of the proposed iteration, are derived explicitly in terms of the reduced nodal admittance matrix, the normalized complex power injections, the no-load voltage profile, and a certified contraction radius. The analysis does not rely on radiality assumptions, parent--child relationships, or backward/forward sweep orderings, and therefore applies uniformly to radial and meshed networks with a unique slack bus, provided that the reduced nodal admittance matrix is nonsingular. The derived contraction factor also yields a priori and a posteriori error bounds, and a simplified sufficient condition is presented for practical verification. The formulation and its convergence certificate are validated on the IEEE 33-bus and IEEE 69-bus radial distribution test feeders, where the method converges to the unique power-flow solution for all tested initial voltage magnitudes, with machine-precision agreement and iteration counts between 11 and 15. The computed power losses and voltage profiles match the classical benchmark results, confirming the correctness, robustness, and practical applicability of the proposed formulation. The proposed approach provides a unified, topology-agnostic framework for power-flow analysis that is particularly suitable for modern distribution systems with high penetration of distributed energy resources.

Downloads

Published

2026-11-15

How to Cite

Montoya, O. D., Ramirez-Vanegas, C. A., & Mesa, F. (2026). A Voltage-Ratio Fixed-Point Formulation for Power Flow Analysis in Single-Phase AC Distribution Networks with Certified Convergence. Statistics, Optimization & Information Computing. https://doi.org/10.19139/soic-2310-5070-4665

Issue

Section

Research Articles

Categories